Virtual Consumer Unit & Dead Testing Simulator

Master the strict statutory testing sequence before entering your practical assessment. Practice safe isolation, lead nulling, $R_1+R_2$ continuity, ring final circuit cross-connection, and 500V DC insulation resistance under simulated workshop conditions.

Step 1: Safe Isolation Procedure (EAWR Reg 14)

Statutory Sequence
Dual RCD Consumer Unit · 230V TN-C-S SupplyBS 7671 Verified
100A Main Switch
ON (Live)
RCD 1 (30mA)
Type A
6A B-Curve
C1: Lights
32A B-Curve
C2: Ring Sockets
40A B-Curve
C3: Shower
16A B-Curve
C4: Water
Earth Bar (MET Connection)
Neutral Bar
MFT-1845 PLUS · DIGITAL MULTIFUNCTION TESTERCALIBRATED · GS38 COMPLIANT
VOLTAGE DETECTORAUTO-RANGE
--- V
READY FOR PROVING

Safe Isolation Protocol

  • 1. Prove 2-pole detector on known proving unit (230V verified)
  • 2. Switch off main supply switch
  • 3. Secure with padlock & caution warning notice tag
  • 4. Test across conductors (L-N, L-E, N-E confirm 0V)
  • 5. Re-check 2-pole detector on proving unit to prove tester still works
⚠️ AM2 / 2391 Critical Failure Point: You will fail your assessment instantly if you do not re-prove your voltage detector on the proving unit *after* testing for dead.